ENM Monitoring and Diagnostics pages display "[Invalid Date]" for timestamps

Issue

The Event Notification Module (ENM) Monitoring and Diagnostics pages display [Invalid Date] in timestamp columns instead of the actual timestamp.

Product Line

ENM 8.3.x

Environment

PowerSCADA Expert 8.1

Power Monitoring Expert 8.1

Cause

Some Windows locales use special characters for AM/PM notation (e.g., Italian [Switzerland], Chinese [Singapore]). When Windows is configured to use one of these locales, ENM cannot properly format timestamps, resulting in [Invalid Date].

Resolution

Change the Windows locale to one that uses standard AM/PM characters.
Examples:

  • Italian (Italy)
  • Chinese (China)

Steps:

  1. Open Control Panel → Region and Language.
  2. Change the locale to a supported setting.
  3. Restart ENM services if necessary.

Notes

  • This issue applies only to ENM 8.x and PME 8.1.
  • Newer versions of PME and ENM have resolved this locale parsing issue.

Recommendation

If you are using an older version of PME or ENM, upgrading to the latest version is strongly recommended. Upgrading provides better compatibility, improved security, and fixes for known issues.
For upgrade assistance, contact: pmo-psup@se.com.

ชไนเดอร์ อิเล็คทริค Thailand

ดูข้อมูลเพิ่มเติม
รุ่น:
ดูข้อมูลเพิ่มเติม
รุ่น:
  • คู่มือผลิตภัณฑ์
  • ดาวน์โหลดซอฟต์แวร์
  • โปรแกรมช่วยเลือกผลิตภัณฑ์
  • ผลิตภัณฑ์ทดแทนและอะไหล่
  • ศูนย์ช่วยเหลือและการติดต่อ
  • ค้นหาสํานักงานของเรา
  • รับใบเสนอราคา
  • สถานที่จัดจำหน่าย
  • ชุมชน Schneider Electric
  • ร่วมงานกับเรา
  • ข้อมูลบริษัท
  • ร้องเรียนการประพฤติมิชอบ
  • การช่วยการเข้าถึง
  • ห้องข่าว
  • นักลงทุน
  • EcoStruxure
  • ค้นหาตำแหน่งงาน
  • บล็อก
  • นโยบายความเป็นส่วนตัว
  • ประกาศเกี่ยวกับคุกกี้
  • ข้อกำหนดการใช้งาน
  • Change your cookie settings