Size bugün nasıl yardımcı olabiliriz?

What are the ATSTCopin and ATSTCopout sections in a legacy project imported into Unity Pro?

Issue:

What are the ATSTCopin and  ATSTCopout sections in a legacy project imported into Unity Pro?

Product Line:

Unity Pro

Resolution:

These ST sections are created when importing a legacy application into Unity Pro with a different PLC as the target PLC family
when the configuration of  the I/O modules cannot be converted into the target PLC's module configuration.
In some cases, ST sections will be created to emulate legacy configuration behavior.

If the address conversion option 'Full Topological' is selected, copying code for the module data between topological address and corresponding areas
in %M or %MW memory is placed into these sections as well.
sections

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings