Video: How to Clear Alarms on an InRow ACRD200 Cooling System
Issue:
How Clear Alarms on an ACRD200 Cooling Unit.

Product line:
InRow Cooling Products ACRD200.

Environment:
All Serial Numbers.

Cause:
Install, Configuration.

Resolution:



First you need to access the Clear Alarms menu you can do this by hitting the <ESC> until visible

Then select ENTER

It will ask if you want to clear alarms select yes

You will be prompted for a Password

Use the default password of “apc”

If this does not work check with your Admin for the correct password

If password has been lost use the last eight digits of the serial number

Now select clear alarms again and again select yes and alarms will be cleared.