{}

Markalar

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
SSS'leri Arayın
Video: How to change name and location of an InRow ACRD200 cooling unit
Issue:
How to change name and location of an ACRD200 cooling unit.

Product line:
InRow ACRD200.

Environment:
All Serial Numbers.

Cause:
Install, Configuration.

Resolution:



Press ESC until you get to the main screen (On/Standby)

Use the Up or Down arrows to find the heading Set Identification

Press ENTER and select Name

Now you will be prompted for a password

Use the default password of “apc”

If this does not work check with your Admin for the correct password

If password has been lost use the last eight digits of the serial number

Press Enter on Name and select any name with 8 characters or less

Press Enter on Location and select any location with 8 characters or less

Schneider Electric Turkey

Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Yardımcı olabilecek makaleler
Schneider Electric Türkiye ile İlgili Ürünler
Seri: