Can SturxureWare Data Centre Expert be integrated into Power Monitoring Expert?

Issue:

User wants to know if StruxureWare Data Center Expert (DCE) can be integrated with Power Monitoring Expert (PME).

Product Line:

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

PME

DCE

EcoStruxure IT Gateway

Cause:

PME does not include a dedicated integration component for DCE. Integration depends on whether DCE can expose data using a protocol PME supports.

Resolution:

  • PME can integrate with DCE only if DCE can be configured as an OPC DA/UA server or as a Modbus TCP device.
  • If DCE does not support these protocols, PME cannot retrieve data directly. In that case, add the specific devices monitored by DCE into PME individually.
  • Contact SE Tech Support at: pmo.support@se.com

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Current availability

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings