Markalar

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.

SSS'leri Arayın

Do the PowerLogic and ION meters support low voltage DC power supplies?

Issue

To determine available DC Low Voltage Supply options for a meter

Product line

Powerlogic Meter
ION Meter

Environment

Power Supply

Resolution
MeterSpecification
ION9000No DC low voltage supply option
ION7550/7650 20-60 V DC
PM8000 series20-60 V DC ±10 %
ION8650/8600Auxiliary DC low voltage supply 80-160 V DC ±20 % only
ION620020-60 V DC
CM4000 seriesNo DC low voltage supply option
PM5000 seriesNo DC low voltage supply option
PM800No DC low voltage supply option
ION7400No DC low voltage supply option
ION770020-60 V DC

Schneider Electric Turkey