Why Incorrect Data values are restored in a Quantum controller with CE V14.1?

"Restore data from File to PLC" is a functionality provided by software "EcoStruxure™ Control Expert".
This functionality is used to restablish the data inside a Quantum PLC before starting a system.


***To read carefully before restoring Data to Quantum controller with Control Expert V14.1.
CAUTION
INCORRECT DATA VALUES RESTORED

With Control Expert V14.1, you must install ControlExpert_V141_HF0570819R HotFix to use the “Restore Data from File to PLC” function with a Quantum controller.

Failure to follow these instructions can result in injury or equipment damage


If you do not install the Hot Fix ControlExpert_V141_HF0570819R, the values of the %M and %MW which have associated variable names are not restored correctly (wrong values are restored).
The availability date of ControlExpert_V141_HF0570819R hotfix is planned end March 2020.


Additional information:
  • Save Data to DTX works correctly and a correct DTX file is generated.
  • The Restore Data function is working correctly for the other cases: %M and %MW without variable names, Unlocated variables and Function Bloc instances.
  • DAT files are not affected by this issue.
  • Controllers other than Quantum are not affected by this issue.
***

This problem doesn't exist in the previous version of ControlExpert_V14.1 .
This problem can be obsevred whatever the OS of the Quantum controller.

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings