{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
When does the INF3 (Internal Serial Link) fault occur in Altivar 61/71 Drive.

The Internal Serial Link Fault (INF3) occurs in Altivar 61/71 Drives when the 24VDC internal power supply is disturbed, causing the reset of microprocessor. The second likely reason is that the communication between the internal boards i.e. Power board, Motor Control board and Application Board is disrupted.

To remove the fault, check the internal connections, tightness of ribbon cable & connectors of internal boards. Also ensure that the power cable and the control cable are separated in the external wiring. Lastly replace the Motor Control Board or the Terminal Board.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: