我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Data Center Expert | How do I update incorrect UPS battery ages?
Issue:
Battery Age for UPS shows incorrectly in StruxureWare Data Center Expert.

Product Line:
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

Environment:
StruxureWare Data Center Expert (All Versions)
APC UPS

Cause:
StruxureWare Data Center Expert polls the battery age from each UPSs Network Management Card (NMC) via SNMP.

Resolution:

Note: Ensure that the date and time are correct on the Network Management Card (NMC) of the UPS and within StruxureWare DCE to be able to accurately display the battery age.
Note: The Battery Age report within StruxureWare DCE may report unknown values if the battery age is not set correctly.

Updating the Last Battery Replacement Date on NMC Firmware version 6.X and newer

1) Log into the UPSs web interface.

2) Status Menu > Battery System  OR Configuration Menu > UPS. Options may differ depending on firmware version.

3) Click on the applicable battery pack.

4) Set the Installation Date.

5) Apply the changes.


Updating the Last Battery Replacement date on NMC Firmware Version 5.X and lower

1) Log into the UPSs web interface.

2) UPS Tab > Configuration Section > general.

3) Set the Last Battery Replacement date.

4) Apply the changes.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings