Why is Event Notification Module (ENM) 8.3.X installation failing at Registering Service Manager?


Issue:
The Event Notification Module (ENM) 8.3.X Installer fails the "Registering Service manager" as shown below.
The SE Server manager Host service will not start if this issue is detected by the installer.



It will continue with the installation and stop with Unsuccessful Configuration
as listed on the screen shot below.



Product Line:
Event Notification Module

Environment:
Event Notification Module Installation

Cause:
The Registering Service Manager TimedOut during the installation and will not allow
the SE Server Manger Host service to start.

Resolution:
The ENM installer fails the "Registering service manager" step, but all components are installed successfully.
The step failed because ENM’s SE Server Manager Host service could not be started due to a port conflict between it and another service called LLWecSvc.exe.
The SE Server Manager Host service is a peripheral service that does not have to be started for a successful installation.
However, it does need to be running during run time of ENM.  When running it allows ENM's core services to be reset from the ENM Configuration web page.

Go to Control Panel/Administrative Tools/Services and stop the LLWecSvc.exe service.
This now allows SE Server Manager Host service to be started.
Choose Try Again on your ENM installation.  The installation will pick up again and complete without any warnings this time.
The LLWecSvc.exe service can then be started back after the installation since it will pick a different port.


More Information on the LLWecSvc.exe service
This LL WecSvc.exe service is under TIBCO LOGLOGIC LESSO ENTERPRISE
LOG COLLECTOR from LogLogic.





施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings