What are the possible causes and remedies for Err4 on ATV212 Drives?
Issue:
Causes and remedies for Err4 on ATV212.

Product Line:
ATV212, ATV21, S-Flex

Resolution:
It is a Main Control Board CPU Error. The Control Board CPU is inoperable. Disconnect Control wire(s) from P24 and PP terminals. Cycle power to the drive.

If problem persists, try to reset the drive using tyP parameter. If VFD will not allow any parameter change then replace the VFD.