{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
How to control the speed of the Altivar 630 Drive with Local HMI?
Issue:
ATV630 speed control with local HMI

Product Line:
Altivar ATV600 and ATV900 series drives

Environment:
All

Cause:
The drive's speed is to be controlled by the local  HMI

Resolution:
Enter the Main Menu of the Drive. Go to Complete Settings then go to Command and Reference. In this Menu, the first parameter is Ref Freq 1 Config which is set to AI1 (Factory default), change this parameter to Ref Freq-Rmt Ter

Main Menu -> Complete Settings -> Command and Reference
-> HMI CMD to Bumpless (Default is Disabled)
-> Ref Freq 1 Config -> Ref Freq-Rmt Term
-> If Start/Stop  from Terminals and Speed control from HMI, Control Mode must be changed to Separate

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: