Issue:
IT equipment comes with mounting rails. All mounting rails have minimum and maximum mounting depths.
Product Line:
NetSheltetr SX
Environment:
All versions and serial ranges.
Cause:
Adding cable management and PDU/accessory mounting rails to a cabinet require the mounting rails to be moved inward.
Since the equipment's mounting rails have a min/max depth specification, at some point it's possible to move the rails inward enough that the equipment will require a short-depth monting rail.
Understanding this ahead of time allows the customer to either move to a deeper cabinet, or order the correct rails. This will help avoid delays.
This issue is most likely to occur with standard depth cabinets, but can also occur in deeper cabinets.
Resolution:
See attached file.
IT equipment comes with mounting rails. All mounting rails have minimum and maximum mounting depths.
Product Line:
NetSheltetr SX
Environment:
All versions and serial ranges.
Cause:
Adding cable management and PDU/accessory mounting rails to a cabinet require the mounting rails to be moved inward.
Since the equipment's mounting rails have a min/max depth specification, at some point it's possible to move the rails inward enough that the equipment will require a short-depth monting rail.
Understanding this ahead of time allows the customer to either move to a deeper cabinet, or order the correct rails. This will help avoid delays.
This issue is most likely to occur with standard depth cabinets, but can also occur in deeper cabinets.
Resolution:
See attached file.
Опубліковано для: Schneider Electric Україна




Потрібна допомога?
Інструмент вибору продукту
Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.
Розрахувати вартість
Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Довідковий центр
Знайдіть усі необхідні ресурси для підтримки в одному місці.