{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
I am getting "Cannot create task" error during startup of Runtime Project and I/O Server stops PowerScada version 7.20 SP1.

I am getting "Cannot create task" error during startup of Runtime Project and I/O Server stops.
This is caused by duplicate IO Device names. This can be verified by reviewing the IO Device names in Units database, if duplicates exist either rename them or delete the unwanted device.


Legacy KB System (APS) Data: RESL211126 V1.0, Originally authored by RaDe on 04/04/2013, Last Edited by RaDe on 04/04/2013
Related ranges: PowerSCADA Expert 7.2

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: