What are the limitations for Peer cop configuration within Premium PLC's?

Peer Cop Limitations:

  • The total number of internal words configured within the node must not exceed 500 words for specific input and 500 words specific output (i.e. 1000 words Total).
  • These blocks of words should be contiguous registers.
  • Up to 32 input and 32 output words per node address on the local bus.

Legacy KB System (APS) Data: RESL170484 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modicon Premium