{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Why am I not able to establish communication with external batteries and my SURT15k/20K UPS?

Issue:

Cannot establish communications with external battery packs

Product Line:

Smart-UPS Online

Environment:

All SURT 15K and 20K models, All Serial Numbers

Cause:

Communications are sometimes slow to initialize when connecting external battery packs.

Resolution:
  • Disconnect all external battery packs - Wait at least 2 minutes
  • Connect first battery pack - Wait at least 2 minutes
  • Connect next battery pack - Wait at least 2 minutes
  • Continue until all battery packs are recognized and communicating with the UPS.

If issue persists, consult your users manual for additional troubleshooting methods.

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: