Video: How to change the set points in an InRow SC system
Issue:
How to change the set points in an ACSC100 unit.

Product line:
ACSC100.

Environment:
All Serial Numbers.

Cause:
Install, Configure.

Resolution:



Press the <ESC> key until you get to the main menu On/Standby

Using the down arrow key scroll until you get to “Set Group Set Points”

Use the <ENTER> key

Enter Password Default=apc

Use the arrows to select character and then use the enter key to go to the next letter. After entering the correct password use enter again.

You can now select any set point and change the value.