Issue:
SOF fault on the Altivar Process Drive
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Principle
This fault appears when an overspeed is present on the drive.
Probable Cause
Note: We've seen a few instances where just changing the two parameters in the Motor parameters menu have corrected the issue. However, please be aware that changing the drive to heavy duty de-rates the drive by one HP class.
SOF fault on the Altivar Process Drive
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Principle
This fault appears when an overspeed is present on the drive.
Probable Cause
- Instability or driving load too high. Typically caused by a load driving the motor to spin faster than the drive is attempting to run it.
- The motor may be turning when the drive gets a run command. Turn on Catch on the Fly
- In the Motor parameters menu (5 Complete Settings -> 5.2 Motor parameters):
- Try changing the [Dual rating] to Heavy Duty
- Try changing the [Motor control type] to U/F VC Standard (available on the ATV6xx)
- Check the motor, gain and stability parameters.
- Check the size of the motor/inverter/load.
- Add a braking resistor.
Note: We've seen a few instances where just changing the two parameters in the Motor parameters menu have corrected the issue. However, please be aware that changing the drive to heavy duty de-rates the drive by one HP class.
Example: A 50HP drive would now be a 40HP drive
Released for: Schneider Electric UK




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.