Ecostruxure Power Commission clear port issue 'Port In Use' error.

Please find port details .

Internal servers ( running on host machine ) URL

Note: If these ports are occupied by any other application then EPC will not run.

So here I am attaching clear port utility file and how to run this utility .

Please ask IT team to run clear port utility as per attached instruction.

ServersURL
NodeLogin servicehttps://localhost:8084
NodeUI servicehttp://localhost:8083
NodeApp servicehttp://localhost:8088
Socket servicehttp://localhost:8089
SPIM servicehttp://localhost:8090
Device servicehttp://localhost:8085



Fix - Please see attached files ClearPort.zip

How to run clear port :
Before running this application make sure that EPC is not running on your computer. The application is attached as a zip file. Please extract the content of the zip file before running the application.

Please see the picture below to execute the attached application.

Port

After running this application, Launch EPC.