Can the QMB326W or QMB366W be converted to accept Class J fuses?

Published date: 11 July 2018

Issue:
How Can a QMB fusible switch be converted to accept Class J fuses?  

Product Line:
QMB fusible panelboards 

Environment
Installation/product features

Resolution:
To convert the QMB326W or QMB366W for use with Class J fuses, relocate the load base assemblies and insulators to the mounting location nearest the line base assemblies.  This information is located on the switch's wiring diagram.