In configuring an NF panelboard on Product Selectors/EQM, does installation of an isolated ground also include the regular ground? What is a six wire configuration?

Published date: 15 June 2020

Issue:
In configuring an NF panelboard on Product Selectors/EQM, does installation of an isolated ground also include the regular ground?  Customer wants a 6 wire panel configuration. What is this?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Both standard ground and isolated ground must be selected separately on the Product Selectors program. A six wire configuration includes (3) phase conductors (1) neutral (1)isolated ground and (1) regular ground.