What ethernet ports are used by System Manager Software (SMS)?

Published date: 27 May 2020

 

text
The user must be an Administrator or PowerUser on the server (for installation the user has to be an Administrator)

> Port 80 has to be open for HTTP access via IIS (access by remote browser)

> Port 8888 has to be open for PowerLogic Network Server (local server only)

> Port 8889 has to be open for Alarm Event Server access (local server only)

> Port 1433 has to be open for the SMS database (local server only)

> Port 1240 has to be open for the Browser Connection Manager (local PC only)

>Port 20978 has to be open for the Alarm Web Service

>Port 502 has to be open for Modbus TCP

>Port 21 has to be open for FTP

>Port 102 has to be open if using TCP/MMS (EGW drivers) 