How to enable the Advanced Reports Database Maintenance in SMS servers for database maintenance.

Published date: 18 May 2020

Product Line
SMS 4.x

Environment
Database management. 

Cause
User wishes to attach, detach, or restore the SMS databases using Advanced Reports Database Maintenance. 

*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system. Always backup the registry before making any changes.*
Resolution
1. Open the registry editor by clicking start > run > type in "regedit" and click Ok.
2. Browse to HKEY_LOCAL_MACHINE\Software\Square D Company\Advanced Reports\Report Database
3. Add a DWORD called ShowAdvancedOptions with a value of 1.

To open the Advanced Reports Database Maintenance, navigate to the following directory:"C\PowerLogic\Advanced Reports\Bin\".
In the directory, run the executable "PowerLogic.Database.RptStgDBMaintService.UI.exe".

Note: The default directory is the C drive unless the install directory was changed during install.

 