How to program an TCP/IP Address into an ECM-RM?

Published date: 19 May 2020

Environment
ECMConfig
ECM-RM
CM2000

Resolution
Use an NR&D (SC-902) cable with a CAB108 wired to the same colors as indicated on the ECM-RM.

  1. Set the ECM-RM to Run mode. (By default this switch is in run mode)
  2. Set your computer to com port to 9600, even, 8, 1.
  3. Use the ECMConfig software.
  4. Type in the IP Address in the designated location
  5. Click Update
  6. Push the reset button on the ECM-RM
  7. Configuration Status will change from Brown to Green indicating that an IP Address has been set in the ECM-RM (This should only take a few seconds).