How long does it take the digital input for logic discrimination (ZSI) to be recognized by the Sepam relay?

Published date: 19 May 2020

Issue
User wishes to know how long it takes the digital input for ZSI to be recognized by Sepam relay

Product Line
Sepam series 20
Sepam series 40
Sepam series 80

Environment
Performance

Resolution
It takes approximately 13 ms (one cycle time of the control reading) operating time for the relay to recognize and react to an input change.

Note: For a Sepam series 20, only input I13 can be used to receive a blocking reception.