How many devices can be attached to my Wiser Network?

Published date: 18 June 2020

Issue:
Customer would like to build or expand a Wiser system for his home and would like to know how many thermostats or other devices can be on the system?

Product Line:
Wiser Home Management System (version 1 EER series USA model)

Environment:
Wiser Home Management System (version 1 EER series USA model)

Cause:
The Zigbee Network among the Wiser Coordinator and the devices has limited data bandwidth.  If there are too many devices, the messages could be slow or the system may crash.

Resolution:
The Wiser Network can support a total of 10 Wiser devices of any kind, in any combination, not including the Coordinator itself.    



 