{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
NIC SW Mismatch alarm in Px4x
Issue:
On boot up, an alarm, "NIC SW Mismatch", appears on the relay's display

Product Line:
Micom Px4x

Environment:
Micom Px4x

Cause:
This alarm appears when a new network card is placed into the Micom without the appropriate firmware being loaded first.

Resolution:
Contact Micom Support to request the appropriate firmware to load into the relay. Please have the full Micom part number and software version before calling.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.