{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}
{}

Schneider Electric USA Website

Welcome to our website.

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Was this helpful?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please check the box"}}}
Search FAQs

How can I increase the starting torque in an ATV32 drive?

Issue:
Customer needs more torque to start the motor.

Product Line:
ATV32

Environment:
All models, all versions

Cause:
Motor requires high starting torque

Resolution:
First verify the motor nameplate information has been set properly (FULL menu: drC submenu: bFr, nPr, UnS, nCr, FrS, nSP).  Test to see if the motor can start the load.
If this is not sufficient, change the MPC (Motor param choice) in the FULL: drC menu from nPr to COS.  Then set the COS parameter in the same menu to match the motor's Power Factor (NOT Service Factor).  Test to see if the motor can start the load.
If additional torque is required change the Ctt parameter (Motor control type) from Std (Standard) to UUC (SVC V - Sensorless Vector Control). Further improvements may be possible by increasing UFr (IR Compensation) in the FULL: SEt menu.
Be cautious when increasing UFr as too high a value can cause instability and may stall the motor.

Pay attention to the display while testing.  
If it flashes or blinks off and on while attempting to run it indicates the drive is in Current Limitation.  You may need to review and possibly increase the CLI parameter setting FULL:SEt.
Explore more

Can't find what you are looking for?

Reach out to our Customer Care team to receive information on technical support, assistance for complaints and more.
Explore more