How do I program an ATV630 relay R2 for a 3 second delay before energizing?

Published date: 29 June 2020

Issue:
ATV630 relay R2 programming for a 3 second delay before energizing

Product Line; 
ATV630

Environment
All serial numbers 

Cause
Customer request. 

Resolution
Access: [Complete settings] [Input/Output] [Relay] [R2 configuration]
Identical to [R2 configuration]   r2 
[R1 Delay time] r2d
R2 activation delay time.     range    0...60,000 ms     3000 = 3 seconds 
The change in state takes effect once the configured time has elapsed when the information becomes true.
The delay cannot be set for the [Operating State “Fault”] FLt assignment; and remains at 0.