How can you set, change or remove the password on the Process drives using the Somove software?

Issue:
Customer wants to reset the password using Somove software.

Product Line:
Somove and Process Drive ATV630 and ATV930.

Environment:
All

Cause:
Reset the password using Somove.

Resolution:

On SoMove, going: Device -> Protection, you have the same features when using keypad`s: Main menu -> 4.Password .
Level1/Level2 corresponds to: PIN1/PIN2.

1. To set the password:


Photo A


2. To change the password:



Photo D

3. To remove password:
photo B


4. Protecting the SoMove file can be done by File/Project properties:



Photo C