What is the CrF fault on the ATV630 and ATV930 drives?

Published date: 15 September 2019

Issue:
CrF fault showing on the display of the ATV630 and ATV930 drives.

Product Line:
ATV630 ATV930

Environment:
All model numbers, all serial numbers

Cause:
Unstable mains voltage, or DC Link capacitors lifetime exceeded

Resolution:
1) Restart the drive (switch off / on the drive)
2) Check and analyze the mains input voltage
3) Check the internal wiring from the mains input to the rectifier / AFC brick