Does the BMXERT1604T support IRIG-B?

Issue
When providing an IRIG-B signal 004/5/6/7 to the ERT, the time source is not received.

Product line
Modicon M580, Modicon M340, Modicon X80

Resolution
The IRIG-B 004/5/6/7 synchronization is supported by our ERT module but it requires RS485 connections (5vdc differential output).

The ERT does not support TTL and modulated signals types.