What Class of fuse does the H227N, H227NR and H227NAWK safety switches accept?

Published date: 14 May 2020

Issue:
Fuse for H227N, H227NR and H227NAWK Safety Switch

Product Line:
Safety Switch

Environment:
Fuse for Safety Switch

Resolution:
These switches accept Class L fuses only. With Class L fuses installed, the switches are UL listed for use on systems with up to 200,000 RMS Symmetrical Amperes available fault current.