Is it possible to defeat or disable ground fault on Masterpact NW with Micrologic 6.0A trip units for primary injection testing?
Issue:
Is there a way to defeat or disable ground fault on a Masterpact NW breaker for primary injection testing?

Product line:
Power circuit breakers

Resolution:
There are two ways to defeat ground fault on the NW breaker for primary injection testing.  You can use the hand held test kit, S33594, or the full function test kit, S33595. Or you can use the looping method to counter the single phase current during primary injection testing. See the attached data bulletin 0600DB9901, page 35, for the looping method, or FAQ Looping Method for Testing Breakers with Ground Fault Trip Units

Schneider Electric USA

Attachment(s)
Field Test and Maint_0600DB9901.pdf [142.88 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings