Schneider Electric USA Website

Welcome to our website.

Select your location

View all   Modicon Quantum PAC
Schneider Eletric 140DII33000C Picture
Discontinued

140DII33000C

Schneider Eletric 140DII33000C Picture
Discontinued
140DII33000C

Modicon Quantum intrinsically safe current input module - 8 I - 1.2 mA…2.1 mA

Show more characteristics
140DII33000C  has not been replaced. Please contact your customer care center for more information.
The maximum number of products that can be compared is 4. Remove already added products.

  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    Intrinsically safe discrete input module
    software designation
    ProWORX
    Unity Pro
    Concept
    software version
    V2.2 and above
    Complementary
    product destination
    In conjunction with products for zone 20, 21 or 22
    discrete input number
    8
    no load voltage
    8 V
    short-circuit current
    8 mA
    switching hysteresis
    0.2 mA
    current state 0 guaranteed
    <= 1.2 mA
    current state 1 guaranteed
    >= 2.1 mA
    switching frequency
    100 Hz
    response time
    1 ms resistive at state 0 to state 1
    1 ms resistive at state 1 to state 0
    internal resistance
    2.5 kOhm
    protection type
    Internal by fuse
    Resistor limited
    isolation between channels and bus
    2500 V for 1 minute DC
    1780 V 47...63 Hz AC
    fault type
    Resistor limited
    hot swapping fallback
    Not allowed per intrinsic safety standards
    power dissipation in W
    2 W
    marking
    CE
    II1 G/D-EEx ia IIC
    bus current requirement
    0.4 A
    module format
    Standard
    net weight
    0.66 lb(US) (0.3 kg)
    Environment
    protective treatment
    Conformal coating Humiseal 1A33
    standards
    UL 508
    EN 50020
    EN 50014
    EN 50039
    EN 50281-1-1
    CSA C22.2 No 142
    Directive ATEX 94/9/EC
    EN 50284
    dust zone
    Outside zone
    product certifications
    FM Class 1 Division 2
    resistance to electrostatic discharge
    4 kV contact IEC 801-2
    8 kV on air IEC 801-2
    resistance to electromagnetic fields
    9.14 V/m (10 V/m) 80...1000 MHz IEC 801-3
    ambient air temperature for operation
    32…140 °F (0…60 °C)
    ambient air temperature for storage
    -40…185 °F (-40…85 °C)
    relative humidity
    95 % without condensation
    operating altitude
    <= 16404.2 ft (5000 m)
    Ordering and shipping details
    Category
    18155-QUANTUM I/O & POWER SUPPLIES
    Discount Schedule
    PC21
    GTIN
    00785901869580
    Returnability
    No
    Country of origin
    US
    Contractual warranty
    Warranty
    18 months
  • View more View less

    Documents

    Language
    • English3
    User guide
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 5.7 MB
    Date 12/1/18
    End of Life Information
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 293 KB
    Date 2/1/16
    Product Environmental Profile
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 17.9 MB
    Date 5/1/15
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1)
    2 slots
    (2)
    3 slots
    (3)
    4 slots
    (4)
    6 slots
    (5)
    10 slots
    (6)
    16 slots


  • Connections and Schema

    Intrinsically Safe Discrete Input Module
    Cenelec Certified Wiring Diagram



Compare products: /