View all
TeSys GV7 Manual Starters and Protectors

GV7RE20
GV7RE20
TeSys GV7 Manual Starter and Protector, thermal magnetic circuit protector, rocker lever, 3 P, AC-3, 12...20 A
Show more characteristics
* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
-
Product availabilityNon-Stock - Not normally stocked in distribution facility
-
Characteristics
Main range TeSysproduct name TeSys GV7device short name GV7Rdevice application Motorpoles description 3Pnetwork type ACutilisation category AC-3 IEC 60947-4-1network frequency 50/60 Hz IEC 60947-4-1breaking capacity 35 kA Icu 440 V AC 50/60 Hz IEC 60947-285 kA Icu 220/240 V AC 50/60 Hz IEC 60947-236 kA Icu 380/415 V AC 50/60 Hz IEC 60947-225 kA Icu 500 V AC 50/60 Hz IEC 60947-28 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % 440 V AC 50/60 Hz IEC 60947-2100 % 220/240 V AC 50/60 Hz IEC 60947-2100 % 380/415 V AC 50/60 Hz IEC 60947-250 % 500 V AC 50/60 Hz IEC 60947-250 % 660/690 V AC 50/60 Hz IEC 60947-2thermal protection adjustment range 12…20 Atrip unit technology Thermal-magneticComplementary mounting mode By screwsBy clipsmounting support RailFlushKit for fixing the switchgearPanel mountingmounting position Verticalmotor power kW 11 kW 500 V AC 50/60 Hz11 kW 660/690 V AC 50/60 Hz15 kW 660/690 V AC 50/60 Hz9 kW 400/415 V AC 50/60 Hz9 kW 500 V AC 50/60 Hz7.5 kW 400/415 V AC 50/60 Hzcontrol type Rocker lever[Ue] rated operational voltage 690 V AC 50/60 Hz IEC 60947-2[Ui] rated insulation voltage 750 V AC 50/60 Hz IEC 60947-2[Ith] conventional free air thermal current 20 A IEC 60947-4-1[Uimp] rated impulse withstand voltage 8 kV IEC 60947-2power dissipation per pole 5 Wpower dissipation per pole 5 Wmechanical durability 50000 cycleselectrical durability 30000 cycles AC-3 440 V In50000 cycles AC-3 440 V In/2maximum operating rate 25 cyc/hrated duty Continuous IEC 60947-4-1connection pitch 1.38 in (35 mm) without spreaders1.77 in (45 mm) with spreadersconnections - terminals bars cable with lug 0.39 in (10 mm) screw bare cable connectors 0.00…0.15 in² (1.5…95 mm²)tightening torque 88.51 lbf.in (10 N.m) screw M6 132.76 lbf.in (15 N.m) bare cable connectors 0.00…0.15 in² (1.5…95 mm²)mechanical robustness Shocks 15 Gn for 11 ms IEC 60068-2-27Vibrations 2.5 Gn, 0...25 Hz IEC 60068-2-6suitability for isolation Yes IEC 60947-1phase failure sensitivity Yes IEC 60947-4-1 § 7-2-1-5-2height 6.34 in (161 mm)width 4.13 in (105 mm)depth 4.37 in (111 mm)net weight 4.43 lb(US) (2.01 kg)Environment standards NF C 79-130EN/IEC 60947-1NF C 63-120EN/IEC 60947-4-1EN/IEC 60947-2NF C 63-650VDE 0113VDE 0660product certifications DNVULprotective treatment TCIP degree of protection IP405 IEC 60529 with terminal shrouds)pollution degree 3ambient air temperature for operation -13…158 °F (-25…70 °C)ambient air temperature for storage -67…203 °F (-55…95 °C)fire resistance 1760 °F (960 °C) IEC 60695-2-1operating altitude 6561.68 ft (2000 m)Ordering and shipping details Category 22366 - MAN STR PROTECTORS-GV1/GV3Discount Schedule I11GTIN 00785901957317Package weight(Lbs) 1.94 kg (4.27 lb(US))Returnability NoCountry of origin CNOffer Sustainability EU RoHS Directive Not applicable, out of EU RoHS legal scopeEnvironmental Disclosure Contractual warranty Warranty 18 months -
View more
Documents
Language- English5
CatalogFormatSizeAdd to My DocumentsDigest 178 Catalog 18: Contactors and Starters-IEC (Version 1.0)DescriptionSection 18 of Digest 178 provides selection and ordering information for IEC contactors and starters - TeSys K, TeSys D, TeSys F, TeSys U, TeSys GV, and TeSys LS1. Replaces Digest 177 section 18; 0100CT1501_SEC-18Size pdfSize 6.8 MBDate 9/13/19DescriptionSection 18 of Digest 178 provides selection and ordering information for IEC contactors and starters - TeSys K, TeSys D, TeSys F, TeSys U, TeSys GV, and TeSys LS1. Replaces Digest 177 section 18; 0100CT1501_SEC-18TeSys GV Series Manual Motor Starters and Protectors Catalog (Version 1.0)DescriptionSchneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection and control.Size pdfSize 10 MBDate 6/29/10DescriptionSchneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection and control.CADFormatSizeAdd to My DocumentsThermal-magnetic circuit-breakers GV7 R with screw clamp terminals, control by rocker lever, from 9 at 110 kW to 400V, from 11 at 132 kW to 500V, from 15 at 200 kW to 660V (Version 1.0)Size zipSize 124.1 KBDate 1/24/07EU RoHS DeclarationFormatSizeAdd to My DocumentsGV7RE20_ROHS_DECLARATIONDescriptionGV7RE20_ROHS_DECLARATIONSize pdfSize 195.3 KBDate 12/15/19DescriptionGV7RE20_ROHS_DECLARATION -
Technical FAQs
No results found.Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later. -
Dimensions Drawings
GV7RDimensions
(1)126 for GV7R●220.Minimum Electrical Clearance
x1
x2
Painted or insulated metal plate, insulation or insulated bar
0
30
Bare metal plate
U ≤ 440 V
5
35
440 V < U < 600 V
10
35
U ≥600 V
20
35
GV7RPanel Mounting
Mounting on 2 Mounting Rails DZ5 MB201
Flush-Mounting
1 circuit breaker GV7R
n circuit breakers GV7R side by side
ConnectionSmooth terminals
a
GV7R●40…R●150
19.5
GV7R●220
21.5
Connectors
-
Connections and Schema
Motor Circuit Breakers
GV7 R