USA
Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Select your location
View all Zelio Time
Schneider Eletric RE11RMXMU Picture
Discontinued

RE11RMXMU

Schneider Eletric RE11RMXMU Picture
Discontinued
RE11RMXMU

time delay relay 9 functions - 1 s..100 h - 24..240 V AC - 1 OC

Show more characteristics
  • Price*
    75.00 USD
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

RE11RMXMU is replaced by:
Product
Qty
RE17RMXMU
Qty
1
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4
  • Reason for Substitution: End of life
  • Substitution date: 01 January 2017
1
  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    component name
    RE11R
    time delay type
    P
    N
    T
    W
    Pt
    Ad
    Ah
    Tt
    O
    time delay range
    0.1...1 s
    6...60 min
    10...100 h
    1...10 h
    6...60 s
    1...10 min
    1...10 s
    [Us] rated supply voltage
    24...240 V AC 50/60 Hz
    24 V DC
    nominal output current
    8 A
    Complementary
    contacts material
    AgNi (cadmium free)
    width pitch dimension
    0.69 in (17.5 mm)
    control type
    Selector switch front panel
    voltage range
    0.85...1.1 Us
    connections - terminals
    Screw terminals, 2 x 1.5 mm² without cable end
    Screw terminals, 2 x 2.5 mm² + 1 x 4 mm² with cable end
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale 25 °C IEC 61812-1
    minimum pulse duration
    100 ms with load in parallel
    30 ms
    maximum reset time
    100 ms on de-energisation
    on-load factor
    100 %
    maximum power consumption
    32 VA 240 V
    maximum power consumption
    0.6 W 24 V
    1.5 W 240 V
    minimum switching current
    10 mA
    maximum switching current
    8 A
    maximum switching voltage
    150 V DC
    250 V AC
    breaking capacity
    2000 VA
    breaking capacity
    80 W
    electrical durability
    100000 cycles 8 A, 250 V resistive
    mechanical durability
    5000000 cycles
    [Uimp] rated impulse withstand voltage
    5 kV 1.2…50 µs IEC 60664-1
    5 kV 1.2…50 µs IEC 61812-1
    marking
    CE
    creepage distance
    4 kV/3 IEC 60664-1
    surge withstand
    1 kV differential mode IEC 61000-4-5 level 3
    2 kV common mode IEC 61000-4-5 level 3
    mounting support
    35 mm symmetrical mounting rail EN 50022
    local signalling
    Flashing: timing in progress LED indicator green)
    On steady: relay energised, no timing in progress LED indicator green)
    Pulsing: relay energised, no timing in progress (except functions Di-D) LED indicator green)
    net weight
    0.13 lb(US) (0.06 kg)
    Environment
    immunity to microbreaks
    10 ms
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
    standards
    IEC 60669-2-3
    73/23/EEC
    IEC 61812-1
    EN 50082-1/2
    93/68/EEC
    89/336/EEC
    EN 50081-1/2
    product certifications
    GL
    CSA
    CULus
    ambient air temperature for storage
    -22…140 °F (-30…60 °C)
    ambient air temperature for operation
    -4…140 °F (-20…60 °C)
    IP degree of protection
    IP20 IEC 60529 terminal block)
    IP40 IEC 60529 housing)
    IP50 IEC 60529 front panel)
    vibration resistance
    0.35 mm 10…55 Hz)IEC 60068-2-6
    relative humidity
    93 % without condensation IEC 60068-2-3
    resistance to electrostatic discharge
    6 kV in contact IEC 61000-4-2 level 3
    8 kV in air IEC 61000-4-2 level 3
    resistance to electromagnetic fields
    9.14 V/m (10 V/m) 80 MHz to 1 GHz ENV 50140/204 level 3
    9.14 V/m (10 V/m) 80 MHz to 1 GHz IEC 61000-4-3 level 3
    resistance to fast transients
    1 kV IEC 61000-4-4 level 3 capacitive connecting clip)
    2 kV IEC 61000-4-4 level 3 direct)
    immunity to radioelectric fields
    10 V 0.15...80 MHz)ENV 50141 (IEC 61000-4-6)
    immunity to voltage dips
    30 % / 10 ms IEC 61000-4-11
    60 % / 100 ms IEC 61000-4-11
    95 % / 5 s IEC 61000-4-11
    disturbance radiated/conducted
    Class B EN 55022 (EN 55011 group 1)
    Ordering and shipping details
    Category
    22370-RE, RM MISC TIMERS & COUNTERS
    Discount Schedule
    CP2
    GTIN
    00785901570745
    Package weight(Lbs)
    0.16 lb(US) (0.073 kg)
    Returnability
    No
    Country of origin
    FR
    Contractual warranty
    Warranty
    18 months
  • View more View less

    Documents

    Language
    • English3
    Catalog
    Format
    Size
    Date
    Add to My Documents
    Zelio Timing Relays Catalog (Version 1.0)
    Description
    This catalog includes information on definitions, selection, functions, catalog numbers, dimensions, and wiring for Zelio™ Timing Relays.
    Size pdf
    Size 2.1 MB
    Date 6/2/10
    Description
    This catalog includes information on definitions, selection, functions, catalog numbers, dimensions, and wiring for Zelio™ Timing Relays.
    CAD
    Format
    Size
    Date
    Add to My Documents
    CAD file (on TraceParts) for RE11RMXMU: time delay relay 9 functions - 1 s..100 h - 24..240 V AC - 1 OC (Version 2.0)
    Description
    You will be redirected to the Traceparts website. Register for free or log in to your Traceparts account to download more than 15 different 2D or 3D CAD formats.
    CAD file (on TraceParts) for RE11RMXMU: time delay relay 9 functions - 1 s..100 h - 24..240 V AC - 1 OC (Version 2.0)
    Description
    You will be redirected to the Traceparts website. Register for free or log in to your Traceparts account to download more than 15 different 2D or 3D CAD formats.
    CAD for RE11RMXMU: time delay relay 9 functions - 1 s..100 h - 24..240 V AC - 1 OC (Version 1.0)
    Description
    You will be redirected to the ThomasNet website. Then you could download this CAD model in more than 15 different 2D or 3D CAD formats.
    CAD for RE11RMXMU: time delay relay 9 functions - 1 s..100 h - 24..240 V AC - 1 OC (Version 1.0)
    Description
    You will be redirected to the ThomasNet website. Then you could download this CAD model in more than 15 different 2D or 3D CAD formats.
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram


    1) Contact Y1:

    • Control for functions B, C, Ac, Bw, Ad, Ah, N, O, W, T, Tt.

    • Partial stop for functions At, Ht and Pt.

    • Function D if Di selected.

    • Not used for functions A, H and P.


  • Technical Description

    Function Ad : Pulse Delayed Relay with Control Signal
    Description

    After power-up, pulsing or maintaining of control contact C starts the timing T.

    At the end of this timing period T, the output R closes.

    The output R will be reset the next time control contact C is pulsed or maintained.

    Function: 1 Output



    Function Ah : Pulse Delayed Relay (Single Cycle) with Control Signal
    Description

    After power-up, pulsing or maintaining of control contact C starts the timing T. A single cycle then starts with 2 timing periods T of equal duration (start with output in rest position).

    Output R closes at the end of the first timing period T and reverts to its initial position at the end of the second timing period T.

    Control contact C must be reset in order to re-start the single flashing cycle.

    Function: 1 Output



    Function N : Retriggerable Interval Relay with Control Signal On
    Description

    After power-up and an initial control pulse C, the output R closes.

    If the interval between two control pulses C is greater than the set timing period T, timing elapses normally and the output R closes at the end of the timing period. If the interval is not greater than the set timing period, the output R remains closed until this condition is met.

    Function: 1 Output



    Function O : Retriggerable Interval Delayed Relay with Control Signal On
    Description

    An initial timing period T begins on energisation. At the end of this timing period, the output R closes.

    As soon as there is a control pulse C, the output R reverts to its initial state until the interval between two control pulses is less than the value of the set timing period T. Otherwise, the output R closes at the end of the timing period T.

    Function: 1 Output



    Function P : Pulse Delayed Relay with Fixed Pulse Length
    Description

    The timing period T begins on energisation.

    At the end of this period, the output R closes for a fixed time P.

    Function: 1 Output


    P = 500 ms


    Function Pt : Pulse Delayed Relay (Summation and Fixed Pulse Length) with Control Signal Off
    Description

    On energisation, timing period T starts (it can be interrupted by operating the Gate control contact G).

    At the end of this period, the output R closes for a fixed time P.

    Function: 1 Output


    T = t1 + t2 + ...

    P = 500 ms


    Function T : Bistable Relay with Control Signal On
    Description

    After power-up, pulsing or maintaining of control contact C switches the output on.

    A second pulse on the control contact C switches the output R off.

    Function: 1 Output



    Function Tt : Retriggerable Bistable Relay with Control Signal On
    Description

    After power-up, pulsing or maintaining of control contact C switches output R on and starts timing T.

    The output switches off at the end of the timing period T or following a second pulse on the control contact C.

    Function: 1 Output



    Function W : Interval Relay with Control Signal Off
    Description

    After power-up and opening of the control contact, the output(s) close(s) for a timing period T.

    At the end of this timing period the output(s) revert(s) to its/their initial state.

    The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply


Compare products: /