Schneider Electric USA Website

Welcome to our website.

Select your location

View all   Modicon Premium PAC
Schneider Eletric TSXPAY282 Picture
Discontinued

TSXPAY282

Schneider Eletric TSXPAY282 Picture
Discontinued
TSXPAY282

Preventa safety module - 24 V DC - standard format - < 5 W

Show more characteristics
TSXPAY282  has not been replaced. Please contact your customer care center for more information.
  • 1,047.00 USD
    Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
The maximum number of products that can be compared is 4

  • Main
    range of product
    Modicon Premium Automation platform
    product or component type
    Preventa safety module
    Complementary
    [Us] rated supply voltage
    24 V DC
    supply voltage limits
    19.2…30 V
    activation threshold
    < 20 V
    short-circuit protection
    1 A gG external IEC 947-5-1 for F1 on power supply
    4 A gG external IEC 947-5-1 for F2 on safety relay outputs
    isolation voltage
    4000 V III 2
    discrete input number
    1 double or single contact selection input IEC 1131 Type 1
    1 feedback loop input IEC 1131 Type 1
    1 reset PB input IEC 1131 Type 1
    1 reset PB monitoring input IEC 1131 Type 1
    12 emergency stop or limit switch discrete inputs IEC 1131 Type 1
    discrete input logic
    Positive
    inrush current
    0.5 A
    isolation between input and earth
    500 Vrms 50/60 Hz 60 s
    maximum power dissipation in W
    5 W
    safety outputs
    4 NO safety relay AGCDO gold plated volt free output
    [Ue] rated operational voltage
    17...127 V DC relay output
    19...250 V AC relay output
    rated power in VA
    120 VA 48 V AC-15 inductive
    280 VA 110 V AC-15 inductive
    550 VA 220 V AC-15 inductive
    60 VA 24 V AC-15 inductive
    rated power in W
    60 W 24 V DC-13 inductive 100 ms
    [Ithe] conventional enclosed thermal current
    2.5 A
    minimum output current
    30 mA
    response time on output
    < 12 ms
    isolation between output and earth
    300 V DIN VDE 0110 part 2
    1500 Vrms 50/60 Hz 60 s
    safety acquisition
    Read feedback loop
    Read enable inputs
    Read the safety outputs control
    Read status of the 24 inputs
    Monitor external power supply of the module
    local signalling
    Diagnostic of safety system 28 LEDs
    electrical connection
    1 connector removable screw terminal block 6 pins
    1 connector SUB-D 44 pins for connecting the safety system
    cable cross section
    0.00…0.00 in² (0.2…2.5 mm²) without cable end safety output circuit
    0.00 in² (1.5 mm²) with cable end safety output circuit
    current consumption
    < 150 mA 5 V DC
    <= 200 mA 24 V DC
    module format
    Standard
    net weight
    1.08 lb(US) (0.49 kg)
    Environment
    ambient air temperature for operation
    32…104 °F (0…40 °C) without fan
    32…140 °F (0…60 °C) with fan module
    ambient air temperature for storage
    -13…158 °F (-25…70 °C)
    IP degree of protection
    IP20 IEC 60529
    standards
    EN 954 machine safety parts of control systems
    EN/IEC 60204-1 machine electrical equipment
    EN/IEC 61131-2 specific requirements (PLC)
    EN/ISO 12100 machine electrical equipment
    ISO 13850 emergency stop equipment
    UL 508 specific requirements (PLC)
    ISO 13849-1 category 4 machine safety parts of control systems
    IEC 61508 SIL 3 machine safety parts of control systems
    CSA C22.2 specific requirements (PLC)
    product certifications
    CSA
    UL
    BG
    Ordering and shipping details
    Category
    22558-TSX PREMIUM, ATRIUM & PL7 PRO
    Discount Schedule
    PC22
    GTIN
    00785901530442
    Returnability
    No
    Country of origin
    FR
    Contractual warranty
    Warranty
    18 months
  • View more View less

    Documents

    Language
    • All Languages4
    • English2
    • French1
    • Spanish1
    User guide
    Format
    Size
    Date
    Add to My Documents
    Premium and Atrium using EcoStruxure™ Control Expert - Discrete I/O modules, User Manual (Version 10)
    Description
    This manual describes the hardware and software implementation of Discrete modules for Premium and Atrium PLCs.
    prp.document.label.format pdf
    Size 5 MB
    Date 12/1/18
    Description
    This manual describes the hardware and software implementation of Discrete modules for Premium and Atrium PLCs.
    Premium and Atrium using EcoStruxure™ Control Expert, Processors, Racks and Power Supply Modules (Version 10)
    Description
    This manual describes the hardware installation of the Premium and Atrium range of PLCs and their main accessories. It contains 6 parts: - General presentation of Premium and Atrium PLC stations, - TSX P57/TSX H57 Premium Processors, - TSX PCI 57 Atrium Processors, - TSX PSY Supply modules, - Process power supply modules, - Standard and extendable TSX RKY racks.
    prp.document.label.format pdf
    Size 3.6 MB
    Date 12/1/18
    Description
    This manual describes the hardware installation of the Premium and Atrium range of PLCs and their main accessories. It contains 6 parts: - General presentation of Premium and Atrium PLC stations, - TSX P57/TSX H57 Premium Processors, - TSX PCI 57 Atrium Processors, - TSX PSY Supply modules, - Process power supply modules, - Standard and extendable TSX RKY racks.
    Premium et Atrium sous EcoStruxure™ Control Expert, Processeurs, racks et modules d'alimentation, Manuel de mise en oeuvre (Version 10)
    Description
    Ce manuel décrit la mise en oeuvre matérielle des automates Premium et Atrium et de leurs accessoires principaux.
    prp.document.label.format pdf
    Size 3.7 MB
    Date 12/1/18
    Description
    Ce manuel décrit la mise en oeuvre matérielle des automates Premium et Atrium et de leurs accessoires principaux.
    Premium y Atrium con EcoStruxure™ Control Expert, Procesadores, bastidores y módulo de fuente de alimentación, Manual de instalación (Version 12)
    Description
    En este manual se describe la instalación del hardware de las gamas Premium y Atrium de PLC y sus principales accesorios
    prp.document.label.format pdf
    Size 3.7 MB
    Date 12/1/18
    Description
    En este manual se describe la instalación del hardware de las gamas Premium y Atrium de PLC y sus principales accesorios
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /