{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?
Issue:
INF8 code, (internal power supply fault) on ATV71

Product Line:
Altivar ATV61 and ATV71

Environment:
All types

Cause:
The control supply voltage is to incorrect.

Resolution:
Check the control supply voltages between +24vdc and com or +24V and 0V.
If using an external supply check +24Vdc supply connect between P24 and 0V, and insure the voltage is greater than 19Vdc and does not exceed 30vdc.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: