You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
SCF is a Short Circuit Fault
Product Line:
ATV58, FLEX58
Environment:
All models and serial numbers
Cause:
Possible causes are:
1. heat sink fans are not operating
2. The output transistors (IGBT) are not gating correctly
3. Short circuit in the motor or motor wiring
4. capacitance due to long motor lengths
Resolution:
1. replace the heat sink fans
2. repair or replace the drive. This drive has been discontinued. Parts may not be available.
3. check motor for shorts, Megger motor and motor wires with minimum of 1000v megger
4. add a load filter