Altivar process catalog issued in May 2014 mention 500 meter shielded cable with du/dt filter, but in new catalog in Sep 2014 it is mentioned 300 meter?

The good length is 300m shielded cable with dv/dt filter in the catalogue of September 2014 is correct. In this case, you should use Dv/Dt filter to reach the 500m without shielded cable.

As per the new catalog information's you can go up to the maximum length of

Shielded cable with dv/dt filter ----> 300 meter
Unshielded cable with dv/dt filter ----> 500 meter
Shielded cable with Sinus filter ----> 500 meter
Un-shielded cable with sinus filter ---->1000 meter