Issue:
What is the Ground leakage current for SCF3 fault?
Product Line:
Altivar 61, Altivar 71
Environment:
All
Cause:
Drive is tripping on SCF3 fault.
Resolution:
The threshold for a SCF3 fault (short-circuit to Ground) is 25% of drive nominal current. It is a hardware detection and it is not adjustable.
What is the Ground leakage current for SCF3 fault?
Product Line:
Altivar 61, Altivar 71
Environment:
All
Cause:
Drive is tripping on SCF3 fault.
Resolution:
The threshold for a SCF3 fault (short-circuit to Ground) is 25% of drive nominal current. It is a hardware detection and it is not adjustable.