{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What would cause ground leakage current on an ATV61 or ATV71?
Issue:
What is the Ground leakage current for SCF3 fault?

Product Line:
Altivar 61, Altivar 71

Environment:
All

Cause:
Drive is tripping on SCF3 fault.

Resolution:
The threshold for a SCF3 fault (short-circuit to Ground) is 25% of drive nominal current. It is a hardware detection and it is not adjustable.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: