Can the Modicon M580 IO Scan nodes on different domains?

Title
 Modicon M580 IO Scan nodes on different domains
 
Issue
 Modicon M580 IO Scan nodes on different domains
 
Product Line
M580
 
Environment
Unity Pro 11.1
 
Cause
N/A
 
Resolution
 It is not possible to IO Scan devices that are located on different domains with the M580 built-in Ethernet port or the BMENOC0301.2 module. Unity pro will display an error saying both IP and gateway should have the same subnetwork mask. To IO Scan devices in different domains requires the use of a BMENOC0301.3  with Unity pro V11.1.
 