{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Why do I have NaN values for PowerTag NSX 3P ?
If you are using a 3P PowerTag NSX on a 3P+N system please check that:
  • you have connected the white wire to the Neutral of your panel
  • the Electrical Network System is defined as 3PH4W under your Smartlink or PowerTag Link Web Interface

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: