{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}
{}

Welcome to the Schneider Electric Website

Welcome to our website.
 

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais

How does the Earth Fault protection work in Micrologic 6.0 when Neutral CT...

When the Neutral CT is not connected, the Earth Fault protection still operates in Micrologic 6.0 trip unit as it works on the principal of vectorial sum calculation of 3 phases. In case of Earth...

What is the difference between XBTZ925 cable and XBTZG925 cable.

Following are the difference between XBTZ925 cable and XBTZG925 cable: 1. XBTZ925A and XBTZ925B, in connection with TSX CUSB45 converter, is used for programming HMI terminals: XBT N/R. 2....

What is the noise level of TeSys D contactors and how to reduce the Noise...

Noise Level: The noise level of TeSys D range of contactor is less than or equal to 35dB. This is one of the control parameters during the testing of the TeSys D contactor. Method for reducing...

Delivery time of Large Order Quantity (LOQ) cannot be provided exactly...

For the Large Order Quantity (LOQ), we encourage you to have the premeditation. If you would like to order a significant amount, we need more time to check with our factory then inform you the...

Learn more through our Generic Knowledge FAQsGeneral Knowledge

What is the part number of the cable used for communication between...

TSXSCPCM4030 cable is required from TSXSCP114 PCMCIA card to the Modbus branching device TSXSCA50 for connecting other RS485 device on the Modbus Network. In case TSXSCA50 Modbus branching device...

Can't find what you are looking for?

Reach out to our Customer Care team to receive information on technical support, assistance for complaints and more.