  • Main
    range
    Masterpact
    product name
    Masterpact MTZ3
    device short name
    MTZ3 40 H2
    product or component type
    Circuit breaker
    device application
    Protection
    poles description
    4P
    neutral position
    Left
    network type
    AC
    network frequency
    50/60 Hz
    breaking capacity code
    H2
    suitability for isolation
    Yes conforming to IEC 60947-2
    selectivity category
    Category B
    Complementary
    control type
    Push-button
    mounting mode
    Drawout
    mounting support
    Base plate
    Rails
    [In] rated current
    4000 A at 40 °C
    [Ui] rated insulation voltage
    1000 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage
    12 kV conforming to IEC 60947-2
    [Icm] rated short-circuit making capacity
    330 kA 220/415 V AC at 50/60 Hz
    330 kA 440 V AC at 50/60 Hz
    286 kA 500/525 V AC at 50/60 Hz
    220 kA 660/690 V AC at 50/60 Hz
    [Ue] rated operational voltage
    690 V AC 50/60 Hz conforming to IEC 60947-2
    circuit breaker CT rating
    4000 A
    performance level
    150 kA Icu at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
    150 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    130 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
    100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    [Ics] rated service breaking capacity
    150 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
    150 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    130 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
    100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    mechanical durability
    10000 cycles with periodic preventive maintenance conforming to IEC 60947-2
    electrical durability
    AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to IEC 60947-3
    1500 cycles 440 V AC 50/60 Hz conforming to IEC 60947-2
    1500 cycles 690 V AC 50/60 Hz conforming to IEC 60947-2
    AC-23A: 1500 cycles 440 V AC 50/60 Hz conforming to IEC 60947-3
    AC-23A: 1500 cycles 690 V AC 50/60 Hz conforming to IEC 60947-3
    connection pitch
    230 mm
    [Icw] rated short-time withstand current
    100 kA 0.5 s conforming to IEC 60947-2
    100 kA 1 s conforming to IEC 60947-2
    100 kA 3 s conforming to IEC 60947-2
    integral instant protection
    243…297 kA
    maximum breaking time
    25 ms
    maximum closing response time
    80 ms
    height
    Drawout circuit breaker without chassis: 300 mm
    Drawout circuit breaker with chassis: 479 mm
    width
    Drawout circuit breaker without chassis: 838 mm
    Drawout circuit breaker with chas