{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
Wiring a 2-wire Transmitter to an STBACI1225 Analog Input

Issue
This resolution describes how to wire 2-wire analog transmitters to the inputs of an STBACI1225 analog input module.


Product Line
Advantys STB
STBACI1225


Environment


Resolution
R2-wire analog transmitters require a loop power supply to power the loop. The following diagram shows how this is done with a single power supply for all current loops.

​​​​​​​


Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: