What is the correct wiring for a 3-wire RTD probe on the BMXART0414 card?

The Unity 4.0 online help file is incorrect. Here is the correct wiring for a three-wire RTD probe (three-wire Channel 6/2):Wiring for a 3-wire RTD ProbeWiring for a 3 wire RTD probe


Legacy KB System (APS) Data: RESL198158 V1.0, Originally authored by TVe on 03/31/2009, Last Edited by TVe on 03/31/2009
Related ranges: Twido