What is a USF fault on ATV61/71?

Published date: 22 January 2020

Issue:
USF fault on ATV61/71.

Product Line:
All drives.

Environment:
All.

Causes:
Low voltage on drive's DC bus.

Resolution:
USF is a mains undervoltage fault that appears when the drive's DC bus goes below a certain value. 
Check the Mains voltage on L1, L2, and L3 with a true RMS meter. 
Measure DC voltage on drive's DC bus PA (+) and PC(-) with meter.