{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
Incorrect Configuration of Report Server Application (SSRS)
Issue:
Receiving the following error message from the Reporting Services Report Server application when
requesting the following ReportServer URL : http://localhost/ReportServer/

Server Error in '/ReportServer' Application
Could not find permission set named 'ASP.Net'.


Product:
Power Monitoring Expert 7.0.1
ION Enterprise 6.0.x
ION EEM

Environment:
Microsoft Reporting Services

Cause:
Although the problem seems to be a SQL Server Reporting Services SSRS problem, actually it is caused by the incorrect configuration of
Report Server application pool in the Internet Information Services IIS web server.

Resolution:
The solution is to change the ASP.net version of the the ReportServer application pool version from 4.0 to 2.0.50727.


Schneider Electric Global

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: